COMPACT TCBB | Cylindrical Cased Axial Flow Fan | Industrial Fan
Ventilation Simplified
  • Contractor
  • Installer
  • Professional Electrician
Back

Compact TCBB

Cylindrical Cased Axial Flow Fan

Compact TCBB

Range of cylindrical cased axial fans fitted with aluminium impellers and manufactured from high grade rolled galvanised steel and protected against corrosion by cataforesis primer and black polyester paint finish.


Features & Benefits

  • Corrosion resistance.
  • Dynamically balanced 'vibration free' impellers.
  • Protected by cataforesis primer.

Range of single phase, 4 pole cylindrical cased axial fans fitted with aluminium impellers and manufactured from high grade rolled galvanised steel. Protected against corrosion by cataforesis primer and black polyester paint finish. Aluminium Impellers are dynamically balanced, according to ISO 1940 standard, providing a vibration free operation.

Electrical Supplies

  • Single phase 230V-50Hz. (Capacitor located inside the wiring terminal box).

Covers a wide range of applications including warehouses, workshops, commercial premises and car parks.

Order code Features / Description Ducting Ø Maximum Airflow l/s (m³/h)
TCBB/4-250H Single phase 4 pole 250 250 (900)
TCBB/4-315H Single phase 4 pole 315 553 (1990)
TCBB/4-355H Single phase 4 pole 355 684 (2462)
TCBB/4-400H Single phase 4 pole 400 1442 (5190)
TCBB/4-450H Single phase 4 pole 450 1892 (6810)
TCBB/4-500H Single phase 4 pole 500 2083 (7500)
TCBB/4-560L Single phase 4 pole 560 3325 (11970)
TCBB/4-560H Single phase 4 pole 560 3600 (12960)
TCBB/4-630H Single phase 4 pole 630 4369 (15730)

We offer a wide range of ancillary products for all ducting sizes. Contact us for further details.

Compact TCBB Fan Dimensions

Model A B C D E Number of Holes N
TCBB/4-250 327 292 170 254 10 4
TCBB/4-315 386 355 170 315 10 8
TCBB/4-355 426 395 170 355 10 8
TCBB/4-400 487 450 170 400 12 8
TCBB/4-450 537 500 180 450 12 8
TCBB/4-500 595 560 180 500 12 12
TCBB/4-560 655 620 240 560 12 12
TCBB/4-630 725 690 240 630 12 12

Dimensions all shown in millimeters.

Q = Air volume in m³/s.
Ps = Static Pressure in mmWG and Pa.
Dry air at 20°C and 760 mmHg.
Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

Typical fan selection:
Do not select the working point in the coloured area. To find the working point it is first necessary to plot the system resistance curve. The working point lies at the intersection between that curve and the fan performance curve.

Example:

Required air volume 13.100 m³/h at 18 mmWG
Fan working point 14.150 m³/h at 21 mmWG

Compact TCBB Performance Curve